- Overview
- Recommended Products
- Pure sine wave output
- DSP digital contro
- Boost and buck AVR for voltage stabilization
- Cold start function
- Intelligent battery management
- Short circuit and overload protection
- Off-mode charging
- Offering LED and LCD panels for selection
- Optional USB, RS232/RJ45/SNMP communication port
TECHNICAL SPECIFICATION:
MODEL | UC1K(S) | |
Capacity | 1000VA/800W | |
INPUT | ||
Voltage range | 145~275VAC±5V | |
Frequency range | 50HZ-60HZ | |
OUTPUT | ||
Output voltage | 220VAC | |
AC voltage range | ±10% | |
Frequency range(Batt.Mode) | 50Hz±0.25Hz or 60Hz±0.3Hz | |
Overload | 105%-110%:UPS beep alamm, do not shut down | |
110%-130%:auto shut down after 30 seconds | ||
>130%:auto shut down immediately | ||
Transfer time | 0ms | |
Wave form(batt.mode) | Pure sine wave | |
BATTERY | ||
Standard model | Battery type | 12V7Ah |
Numbers | 2 | |
Charging current(Max.) | Assume:1A±10% Max: 1A or 2A for option | |
Charging voltage | 27.3VDC±1% | |
Long-run model | Battery type | 12V,AH depending on applicant |
Numbers | 3 | |
Charging current(Max.) | > 5A | |
Charging voltage | 27.4VDC±1% | |
PHYSICAL | ||
Standard model | Dimension LxWxH(mm) | 360x147x220 |
Net weight(kgs) | 11.9 | |
Long-run model | Dimension LxWxH(mm) | 360x147x220 |
Net weight(kgs) | 8.5 | |
ENVIRONMENT | ||
Humidity | 20-90%RH@0-40℃(non-condensing) | |
Noise level | Less than 55dBA@1 Meter | |
MANAGEMENT | ||
Smart RS-232 | Support windows 2000/2003/XP/Vista/2008, Windows7/8, Linux, Unix, and MAC | |
Optional SNMP | Power management from SNMP management and web browser |
TECHNICAL SPECIFICATION:
MODEL | UC2K(S) | |
Capacity | 2000VA/1600W | |
INPUT | ||
Voltage range | 145~275VAC±5V | |
Frequency range | 50HZ-60HZ | |
OUTPUT | ||
Output voltage | 220VAC | |
AC voltage range | ±10% | |
Frequency range(Batt.Mode) | 50Hz±0.25Hz or 60Hz±0.3Hz | |
Overload | 105%-110%:UPS beep alamm, do not shut down | |
110%-130%:auto shut down after 30 seconds | ||
>130%:auto shut down immediately | ||
Transfer time | 0ms | |
Wave form(batt.mode) | Pure sine wave | |
BATTERY | ||
Standard model | Battery type | 12V7Ah |
Numbers | 4 | |
Charging current(Max.) | Assume:1A±10% Max: 1A or 2A for option | |
Charging voltage | 54.7VDC±1% | |
Long-run model | Battery type | 12V,AH depending on applicant |
Numbers | 6 | |
Charging current(Max.) | > 5A | |
Charging voltage | 82.1VDC±1% | |
PHYSICAL | ||
Standard model | Dimension LxWxH(mm) | 440x192x340 |
Net weight(kgs) | 22 | |
Long-run model | Dimension LxWxH(mm) | 440x192x340 |
Net weight(kgs) | 16 | |
ENVIRONMENT | ||
Humidity | 20-90%RH@0-40℃(non-condensing) | |
Noise level | Less than 55dBA@1 Meter | |
MANAGEMENT | ||
Smart RS-232 | Support windows 2000/2003/XP/Vista/2008, Windows7/8, Linux, Unix, and MAC | |
Optional SNMP | Power management from SNMP management and web browser |
TECHNICAL SPECIFICATION:
MODEL | UC3K(S) | |
Capacity | 3000VAV2400W | |
INPUT | ||
Voltage range | 145~275VAC±5V | |
Frequency range | 50HZ-60HZ | |
OUTPUT | ||
Output voltage | 220VAC | |
AC voltage range | ±10% | |
Frequency range(Batt.Mode) | 50Hz±0.25Hz or 60Hz±0.3Hz | |
Overload | 105%-110%:UPS beep alamm, do not shut down | |
110%-130%:auto shut down after 30 seconds | ||
>130%:auto shut down immediately | ||
Transfer time | 0ms | |
Wave form(batt.mode) | Pure sine wave | |
BATTERY | ||
Standard model | Battery type | 12V7Ah |
Numbers | 6 | |
Charging current(Max.) | Assume:1A±10% Max: 1A or 2A for option | |
Charging voltage | 82.0VDC±1% | |
Long-run model | Battery type | 12V,AH depending on applicant |
Numbers | 8 | |
Charging current(Max.) | > 5A | |
Charging voltage | 109.4VDC±1% | |
PHYSICAL | ||
Standard model | Dimension LxWxH(mm) | 440x192x340 |
Net weight(kgs) | 27.9 | |
Long-run model | Dimension LxWxH(mm) | 440x192x340 |
Net weight(kgs) | 18.2 | |
ENVIRONMENT | ||
Humidity | 20-90%RH@0-40℃(non-condensing) | |
Noise level | Less than 55dBA@1 Meter | |
MANAGEMENT | ||
Smart RS-232 | Support windows 2000/2003/XP/Vista/2008, Windows7/8, Linux, Unix, and MAC | |
Optional SNMP | Power management from SNMP management and web browser |
TECHNICAL SPECIFICATION:
MODEL | UC6K(S) | |
Capacity | 6000VA/4.8KW | |
INPUT | ||
Voltage range | 165-275VAC±5V | |
Frequency range | 50HZ-60HZ | |
OUTPUT | ||
Output voltage | 220VAC | |
AC voltage range | ±10% | |
Frequency range(Batt.Mode) | 50Hz±0.25Hz or 60Hz±0.3Hz | |
Overload | 105%-110%:UPS beep alamm, do not shut down | |
110%-130%:auto shut down after 30 seconds | ||
>130%:auto shut down immediately | ||
Transfer time | 0ms | |
Wave form(batt.mode) | Pure sine wave | |
BATTERY | ||
Standard model | Battery type | 12V7Ah |
Numbers | / | |
Charging current(Max.) | Assume:1A±10% Max: 1A or 2A for option | |
Charging voltage | 218.4V±1% | |
Long-run model | Battery type | 12V,AH depending on applicant |
Numbers | 16 | |
Charging current(Max.) | > 5A | |
Charging voltage | 218.4V±1% | |
PHYSICAL | ||
Standard model | Dimension LxWxH(mm) | / |
Net weight(kgs) | / | |
Long-run model | Dimension LxWxH(mm) | 520x240x460 |
Net weight(kgs) | 30.5 | |
ENVIRONMENT | ||
Humidity | 20-90%RH@0-40℃(non-condensing) | |
Noise level | Less than 55dBA@1 Meter | |
MANAGEMENT | ||
Smart RS-232 | Support windows 2000/2003/XP/Vista/2008, Windows7/8, Linux, Unix, and MAC | |
Optional SNMP | Power management from SNMP management and web browser |
TECHNICAL SPECIFICATION:
MODEL | UC10K(S) | |
Capacity | 10KVA/8KW | |
INPUT | ||
Voltage range | 165-275VAC±5V | |
Frequency range | 50HZ-60HZ | |
OUTPUT | ||
Output voltage | 220VAC | |
AC voltage range | ±10% | |
Frequency range(Batt.Mode) | 50Hz±0.25Hz or 60Hz±0.3Hz | |
Overload | 105%-110%:UPS beep alamm, do not shut down | |
110%-130%:auto shut down after 30 seconds | ||
>130%:auto shut down immediately | ||
Transfer time | 0ms | |
Wave form(batt.mode) | Pure sine wave | |
BATTERY | ||
Standard model | Battery type | 12V7Ah |
Numbers | / | |
Charging current(Max.) | Assume:1A±10% Max: 1A or 2A for option | |
Charging voltage | 218.4V±1% | |
Long-run model | Battery type | 12V,AH depending on applicant |
Numbers | 16 | |
Charging current(Max.) | > 5A | |
Charging voltage | 218.4V±1% | |
PHYSICAL | ||
Standard model | Dimension LxWxH(mm) | / |
Net weight(kgs) | / | |
Long-run model | Dimension LxWxH(mm) | 520x240x460 |
Net weight(kgs) | 35 | |
ENVIRONMENT | ||
Humidity | 20-90%RH@0-40℃(non-condensing) | |
Noise level | Less than 55dBA@1 Meter | |
MANAGEMENT | ||
Smart RS-232 | Support windows 2000/2003/XP/Vista/2008, Windows7/8, Linux, Unix, and MAC | |