C6KVA-30KVA
-
Real-time Dual Conversion
-
Microprocessor control ensures high reliability
-
Power factor up to 0.9
-
Wide input voltage range(110V-300V)
-
Output sine wave,compatible with generators
- Optional SNMP card for independent or seamless monitoring with RS232
- Overview
- Recommended Products
APPLICATIONS FIELDS
Widely used in network management centers and computers, banks, securities, taxation, communications, postal services, radio and television, public security, transportation, electric power, medical, industrial control, national defense and other important data fields.
Products specifications:
Model | C6K(S) | |
Phase | Single-input single-output | |
Capacity | 6KVA 5400W | |
Input | ||
Input Voltage | 208/220/230/240VAC | |
Voltage range | 110-300VAC @ 50% load 176-300VAC @ 100% load | |
Input Frequency | 46~54Hz or 56~64Hz | |
Power Factor | ≥0.99@100%load | |
Output | ||
Output Voltage | 208/220/230/240VCA | |
AC voltage regulation | ±1% | |
Frequency (Synchronous correction range) | 46-54Hz/56-64Hz | |
Frequency Range (Battery Mode) | 50Hz/60Hz±0.1Hz | |
Surge Rating | 3:1(max) | |
Waveform balance | ≤3%THD (Linear Load ) ≤5% THD (Non-linear Load) | |
Transfer Time | 0ms | |
Output Waveform | Pure Sine Wave | |
Efficiencies | ||
Mains Mode | 93% | |
Battery Mode | 90% | |
Battery | ||
Stardard UPS |
Battery Model | 12V/7AH |
Battery quantity | 16 | |
Charging time | 9 hours to 90% full capacity | |
Max Charging Current | Preset1A , 1A/2A 4A adjustable | |
Charging voltage | 218.4VDC±1%/273VDC±1% | |
External battery UPS |
Battery Model | Depends on the applicant |
Battery quantity | 16-20 adjustable | |
Max charging current | 1A/2A/4A/6A adjustable | |
Charging voltage | 218.4VDC±1%, 273VDC±1% | |
Display Instructions |
||
LCD |
Load size, battery capacity, mains mode, battery mode, bypass mode, fault indication | |
Physical performance |
||
Stardard UPS |
Size (MM) | 500*248*616 |
Weight (KG) | 57 | |
External battery UPS |
Size (MM) | 500*248*460 |
Weight (KG) | 18 | |
Usage environment |
||
Humidity |
20-95%RH@0-45℃ (No condensation) | |
Noise |
<60dbA@1M | |
Control Management |
||
Smart RS-232/USB |
Be in favor of Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, and MAC | |
Optional SNMP |
Power management supports SNMP management and network management |
Products specifications:
Model | C10K(S) | |
Phase |
Single-input single-output | |
Capacity | 10KVA 9000W | |
Input | ||
Input Voltage | 208/220/230/240VAC | |
Voltage range | 110-300VAC @ 50% load 176-300VAC @ 100% load | |
Input Frequency | 46~54Hz or 56~64Hz | |
Power Factor | ≥0.99@100%load | |
Output | ||
Output Voltage | 208/220/230/240VCA | |
AC voltage regulation | ±1% | |
Frequency (Synchronous correction range) | 46-54Hz/56-64Hz | |
Frequency Range (Battery Mode) | 50Hz/60Hz±0.1Hz | |
Surge Rating | 3:1(max) | |
Waveform balance | ≤3%THD (Linear Load ) ≤5% THD (Non-linear Load) | |
Transfer Time | 0ms | |
Output Waveform | Pure Sine Wave | |
Efficiencies | ||
Mains Mode | 94% | |
Battery Mode | 91% | |
Battery | ||
Stardard UPS |
Battery Model | 12V/7AH |
Battery quantity | 16 | |
Charging time | 9 hours to 90% full capacity | |
Max Charging Current | Preset1A , 1A/2A 4A adjustable | |
Charging voltage | 218.4VDC±1%/273VDC±1% | |
External battery UPS |
Battery Model | Depends on the applicant |
Battery quantity | 16-20 adjustable | |
Max charging current | 1A/2A/4A/6A adjustable | |
Charging voltage | 218.4VDC±1%, 273VDC±1% | |
Display Instructions |
||
LCD |
Load size, battery capacity, mains mode, battery mode, bypass mode, fault indication | |
Physical performance |
||
Stardard UPS |
Size (MM) | 500*248*616 |
Weight (KG) | 68 | |
External battery UPS |
Size (MM) | 500*248*460 |
Weight (KG) | 20 | |
Usage environment |
||
Humidity |
20-95%RH@0-45℃ (No condensation) | |
Noise |
<60dbA@1M | |
Control Management |
||
Smart RS-232/USB |
Be in favor of Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, and MAC | |
Optional SNMP |
Power management supports SNMP management and network management |
Products specifications:
Model | 3C 10K(S) | |
Phase | Three-input single-output | |
Capacity | 10KVA 8000W | |
Input | ||
Input Voltage | 380/400VAC/415VAC (3ph + N) | |
Voltage range | 190-520VAC (3-phase + N) @ 50% load 305-520VAC (3-phase) @ 100% load | |
Input Frequency | 46~54Hz or 56~64Hz | |
Power Factor | ≥0.8@100%load | |
Output | ||
Output Voltage | 208/220/230/240VCA | |
AC voltage regulation | ±1% | |
Frequency (Synchronous correction range) | 46-54Hz/56-64Hz | |
Frequency Range (Battery Mode) | 50Hz/60Hz±0.2Hz | |
Surge Rating | 3:1(max) | |
Waveform balance | ≤3%THD (Linear Load ) ≤5% THD (Non-linear Load) | |
Transfer Time | 0ms | |
Output Waveform | Pure Sine Wave | |
Efficiencies | ||
Mains Mode | 91% | |
Battery Mode | 91% | |
Battery | ||
Stardard UPS |
Battery Model | 12V/7AH |
Battery quantity | 16/20 | |
Charging time | 9 hours to 90% full capacity | |
Max Charging Current | Preset1A , 1A/2A 4A adjustable | |
Charging voltage | 218.4VDC±1%/273VDC±1% | |
External battery UPS |
Battery Model | Depends on the applicant |
Battery quantity | 16-20 adjustable | |
Max charging current | 1A/2A/4A adjustable | |
Charging voltage | 218.4VDC±1%, 273VDC±1% | |
Display Instructions |
||
LCD |
Load size, battery capacity, mains mode, battery mode, bypass mode, fault indication | |
Physical performance |
||
Stardard UPS |
Size (MM) | 500*248*620 |
Weight (KG) | ||
External battery UPS |
Size (MM) | 575*248*620 |
Weight (KG) | 27 | |
Usage environment |
||
Humidity |
20-95%RH@0-45℃ (No condensation) | |
Noise |
<60dbA@1M | |
Control Management |
||
Smart RS-232/USB |
Be in favor of Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, and MAC | |
Optional SNMP |
Power management supports SNMP management and network management |
Products specifications:
Model | 3C 15K(S) | |
Phase | Three-input single-output | |
Capacity | 15KVA 12000W | |
Input | ||
Input Voltage | 380/400VAC/415VAC (3ph + N) | |
Voltage range | 190-520VAC (3-phase + N) @ 50% load 305-520VAC (3-phase) @ 100% load | |
Input Frequency | 46~54Hz or 56~64Hz | |
Power Factor | ≥0.8@100%load | |
Output | ||
Output Voltage | 208/220/230/240VCA | |
AC voltage regulation | ±1% | |
Frequency (Synchronous correction range) | 46-54Hz/56-64Hz | |
Frequency Range (Battery Mode) | 50Hz/60Hz±0.2Hz | |
Surge Rating | 3:1(max) | |
Waveform balance | ≤3%THD (Linear Load ) ≤5% THD (Non-linear Load) | |
Transfer Time | 0ms | |
Output Waveform | Pure Sine Wave | |
Efficiencies | ||
Mains Mode | 91% | |
Battery Mode | 91% | |
Battery | ||
Stardard UPS |
Battery Model | 12V/7AH |
Battery quantity | 16/20 | |
Charging time | 9 hours to 90% full capacity | |
Max Charging Current | Preset1A , 1A/2A 4A adjustable | |
Charging voltage | 218.4VDC±1%/273VDC±1% | |
External battery UPS |
Battery Model | Depends on the applicant |
Battery quantity | 16-20 adjustable | |
Max charging current | 1A/2A/4A adjustable | |
Charging voltage | 218.4VDC±1%, 273VDC±1% | |
Display Instructions |
||
LCD |
Load size, battery capacity, mains mode, battery mode, bypass mode, fault indication | |
Physical performance |
||
Stardard UPS |
Size (MM) | 500*248*620 |
Weight (KG) | ||
External battery UPS |
Size (MM) | 575*248*620 |
Weight (KG) | 35 | |
Usage environment |
||
Humidity |
20-95%RH@0-45℃ (No condensation) | |
Noise |
<60dbA@1M | |
Control Management |
||
Smart RS-232/USB |
Be in favor of Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, and MAC | |
Optional SNMP |
Power management supports SNMP management and network management |
Products specifications:
Model | 3C 20K(S) | |
Phase | Three-input single-output | |
Capacity | 20KVA 16000W | |
Input | ||
Input Voltage | 380/400VAC/415VAC (3ph + N) | |
Voltage range | 190-520VAC (3-phase + N) @ 50% load 305-520VAC (3-phase) @ 100% load | |
Input Frequency | 46~54Hz or 56~64Hz | |
Power Factor | ≥0.8@100%load | |
Output | ||
Output Voltage | 208/220/230/240VCA | |
AC voltage regulation | ±1% | |
Frequency (Synchronous correction range) | 46-54Hz/56-64Hz | |
Frequency Range (Battery Mode) | 50Hz/60Hz±0.2Hz | |
Surge Rating | 3:1(max) | |
Waveform balance | ≤3%THD (Linear Load ) ≤5% THD (Non-linear Load) | |
Transfer Time | 0ms | |
Output Waveform | Pure Sine Wave | |
Efficiencies | ||
Mains Mode | 93% | |
Battery Mode | 92% | |
Battery | ||
Stardard UPS |
Battery Model | 12V/7AH |
Battery quantity | 16/20 | |
Charging time | 9 hours to 90% full capacity | |
Max Charging Current | Preset1A , 1A/2A 4A adjustable | |
Charging voltage | 218.4VDC±1%/273VDC±1% | |
External battery UPS |
Battery Model | Depends on the applicant |
Battery quantity | 16-20 adjustable | |
Max charging current | 1A/2A/4A adjustable | |
Charging voltage | 218.4VDC±1%, 273VDC±1% | |
Display Instructions |
||
LCD |
Load size, battery capacity, mains mode, battery mode, bypass mode, fault indication | |
Physical performance |
||
Stardard UPS |
Size (MM) | 500*248*620 |
Weight (KG) | ||
External battery UPS |
Size (MM) | 575*248*620 |
Weight (KG) | 35 | |
Usage environment |
||
Humidity |
20-95%RH@0-45℃ (No condensation) | |
Noise |
<60dbA@1M | |
Control Management |
||
Smart RS-232/USB |
Be in favor of Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, and MAC | |
Optional SNMP |
Power management supports SNMP management and network management |
Products specifications:
Model | 3C 30K(S) | |
Phase | Three-input single-output | |
Capacity | 30KVA 24000W | |
Input | ||
Input Voltage | 380/400VAC/415VAC (3ph + N) | |
Voltage range | 190-520VAC (3-phase + N) @ 50% load 305-520VAC (3-phase) @ 100% load | |
Input Frequency | 46~54Hz or 56~64Hz | |
Power Factor | ≥0.8@100%load | |
Output | ||
Output Voltage | 208/220/230/240VCA | |
AC voltage regulation | ±1% | |
Frequency (Synchronous correction range) | 46-54Hz/56-64Hz | |
Frequency Range (Battery Mode) | 50Hz/60Hz±0.2Hz | |
Surge Rating | 3:1(max) | |
Waveform balance | ≤3%THD (Linear Load ) ≤5% THD (Non-linear Load) | |
Transfer Time | 0ms | |
Output Waveform | Pure Sine Wave | |
Efficiencies | ||
Mains Mode | 91% | |
Battery Mode | 90% | |
Battery | ||
Stardard UPS |
Battery Model | |
Battery quantity | ||
Charging time | 9 hours to 90% full capacity | |
Max Charging Current | Preset1A , 1A/2A 4A adjustable | |
Charging voltage | 218.4VDC±1%/273VDC±1% | |
External battery UPS |
Battery Model | Depends on the applicant |
Battery quantity | 16-20 adjustable | |
Max charging current | 1A/2A/4A adjustable | |
Charging voltage | 218.4VDC±1%, 273VDC±1% | |
Display Instructions |
||
LCD |
Load size, battery capacity, mains mode, battery mode, bypass mode, fault indication | |
Physical performance |
||
Stardard UPS |
Size (MM) | |
Weight (KG) | ||
External battery UPS |
Size (MM) | 815*250*826 |
Weight (KG) | 64 | |
Usage environment |
||
Humidity |
20-95%RH@0-45℃ (No condensation) | |
Noise |
<60dbA@1M | |
Control Management |
||
Smart RS-232/USB |
Be in favor of Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, and MAC | |
Optional SNMP |
Power management supports SNMP management and network management |